Electrical Safety and Preventive Measures
- 30 ma used for portable tools (1 Ampere = 1000 MA)
- 1 ohm required for Diesel Generator or portable diesel engines
- 25 mili ohms is enough to kill a person
- Min 3 mtrs clearance from electric to the person when passing. HV
- Low voltage. <250 V
- Medium voltage. 250 V – 650 V
- High voltage. 650 V – 33 KV
- Extra high voltage. Above 33 KV
Precaution:
- PTW
- Isolation
- LOTO
- Insulation
- RCD (Residual current device) circuit breaker
- Bonding & Grounding
- Guarding
- Electric resistant PPE’s
- Safe work practice
- ELCB (Earth leakage circuit breaker)
- GFCI (Ground fault circuit interrupter)
- OCB (oil circuit breaker)
- VCB (Vacuum circuit breaker)
- Use flameproof apron while putting ON/OFF
Points to Remember:
- The equipment itself should be checked to ensure that it is suitable and conforms with recognized standards such as CE marking and European standards,
- Vertical clearance above walkways shall not be less than 3 mtrs (10ft) for circuits carrying 600 volts or less.
- Current: the flow of electricity through a conductor
- Voltage: the potential difference between two points of a conductor
- HIPOT TEST: It is the insulation leakage test done for high voltage electrical
Standard Electric Boards Colour Code:
- Purple. 24 v dc
- Yellow. 110 v ac
- Blue. 220 v ac
- Red. 440 v ac
Effects of Amount of A/C Current 60 Cycles/Seconds:
- More than 3 ma. Painful shock, incident, accident
- More than 10 ma. muscle contraction can’t go
- 25 mA can kill a person
- More than 30 ma. Temporary lung paralysis
- More than 50 ma. Heart dysfunction, usually fatal
- More than 100 ma – 4 a. Heart dysfunction, fatal
- Over 4 a. heart paralysis, severe. burn
- 50 – 100 a. for a person will be fatal.
- For earth rod (D.G. or welding gen) required 1 ohm
- ARC: Electrical passing through the air
- Minimum acceptable value of insulation resistance, 1 megohm for each 1000 V
- e.g. one motor 2400 V so you should have a minimum insulence resistance megohms
- Clearance a person from live 50 kv lines shall be 10 feet 0.4 inches
Difference Between Grounding & Bonding?
Earthing is the attachment of a bonded metallic system to earth, typically through ground rods or other suitable grounding electrodes. The NEC prohibits earthing via isolated ground rods. As the only means of equipment grounding.
- Transformer requires min 4 earthing.
- Grounding deep 10.
- Ground rods shall not be less than 5/8 inch in diameter by 8 feet in length.
- Ground rods shall be driven into the ground so that one end of the ground rod is at a minimum depth of 8 feet below the surface of the ground.
- Distance (away) from other grounding is 50.
- Rod: copper or galvanized
- Transformer requires min 4 earthing standard ground resistance value of 5.0 ohms or less
- Bonding: grounding one equipment’s to another to avoid static electricity
- The telecommunications industry has often used 5 ohms or less as their value for grounding and bonding while electric utilities construct their ground systems so that the resistance at a large station will be no more than a few tenths of one ohm.
- Platform wide enough with guard rails (39 – 43”) and toe boards (4’’ - 6”)
Download File
No comments:
Post a Comment